Air FiltersCOSHH Regulations The components of filters are inherently safe, but changing air filters could expose operators to a 'Nuisance Dust' hazard. We would therefore recommend that filter changing be carried out by maintenance personnel wearing simple dust masks, eye protection, overalls or protective clothing & gloves. Dirty filters should be sealed into plastic bags for disposal. Disposable Filters These are supplied in the forms of panel & bag filters and are fitted into steel channel runners. Filters are simply withdrawn through the access door by sliding the filter along the channel runner. Filters should generally be replaced when the pressure drop increases to 0.5"wg (125pa) above the initial level. Washable Panel Filters Generally as per disposable filters except when pressure drop indicates dirty filter conditions, filters should be fully immersed in warm water to winch a mild detergent has been added. Agitate the filter until clean, rinse and allow to dry before replacing. HEPA Filters (High Efficiency Particle Arrestors) This type of filter is generally fitted in front withdrawal frame. Filters will be held into the frame by retaining bars which can be removed to allow access to replace filters. Carbon Filters Carbon filters normally have an active life of about twelve (12) months, or more. It is advisable to remove a sample from the pack to return to manufacturer to determine the remaining working life, preferably after the first six (6) months & subsequent six (6) monthly intervals. NOTE! WHEN REPLACING ALL FILTERS ENSURE FILTER IS FACING CORRECT DIRECTION AS INDICATED BY AN AIRFLOW ARROW. |